7 Operation
Maschinenfabrik Reinhausen GmbH 2019
99
5163667/06 EN
ETOS
®
IM
The device only processes commands via digital inputs or the control sys-
tem when it is in the Remote mode. You must also set the Remote behavior
[
Section 7.2.5, Page 96] parameter accordingly.
Setting the desired value
To set the desired value, proceed as follows:
1. Go to
Settings > Parameters > Control > Desired value
.
2. Enter desired value.
3. Press the
Accept
button to save the modified parameter.
Selecting a desired value
You can use this parameter to select the desired value used for control.
To select the desired value, proceed as follows:
1. Go to
Settings > Parameters > Control > Select desired value
.
2. Select the desired value you want in the list.
3. Press the
Accept
button to save the modified parameter.
7.3.1.4 Analog setting of the desired value
With the analog setting of the desired value, the desired value for the auto-
matic voltage regulation can be variably adapted using an analog signal (e.g.
4...20 mA).
Max.
Min.
Desired value
Max.
Min.
Analog signal
Figure 88: Analog setting of the desired value
In order to configure the analog setting of the desired value, you can set the
parameters as described below.