7 Operation
Maschinenfabrik Reinhausen GmbH 2019
142
5163667/06 EN
ETOS
®
IM
7.7.2 Configuring parallel operation
In the
Parallel operation
menu item, you can set the parameters needed for
parallel transformer operation.
Figure 100: Setting parallel operation
The following sections describe how you can set the parameters.
7.7.2.1 Activating parallel operation
You can use this parameter to activate or deactivate parallel operation.
To activate or deactivate parallel operation, proceed as follows:
1. Go to
Settings > Parameters > Parallel operation > Activate parallel
operation
.
2. Select the option you want from the list field.
3. Press the
Accept
button to save the modified parameter.