![MR ETOS IM Operating Instructions Manual Download Page 118](http://html.mh-extra.com/html/mr/etos-im/etos-im_operating-instructions-manual_1844393118.webp)
7 Operation
Maschinenfabrik Reinhausen GmbH 2019
118
5163667/06 EN
ETOS
®
IM
Phase angle correction
You can use this parameter to set the phase angle correction for your trans-
former circuit. To do so, proceed as follows:
1. Go to
Settings > Parameters > Transformer data > Phase angle cor-
rection
.
2. Select the desired option.
3. Press the
Accept
button to save the modified parameter.
Voltage-transformer circuit
You can use this parameter to set your voltage transformer's circuit. You can
select the following options:
Option
Description
1 Ph phase voltage
Measurement in 1-phase grid between
the conductor and neutral conductor.
3 Ph differential voltage
Measurement in 3-phase grid between 2
conductors
3 Ph phase voltage
Measurement in 3-phase grid between
conductor and neutral conductor
Table 19: Voltage-transformer circuit
To set the voltage-transformer circuit, proceed as follows:
1. Go to
Settings > Parameters > Transformer data > Voltage-trans-
former circuit
.
2. Select the desired option.
3. Press the
Accept
button to save the modified parameter.
Current-transformer circuit
You can use this parameter to set the circuit for your current transformer.
You can select the following options:
Option
Description
1 Ph phase current
Measurement of phase current in 1-phase
grid.
3 Ph total current
Measurement of differential current in 3-
phase grid.
3 Ph phase current
Measurement of phase current in 3-phase
grid.
Table 20: Current-transformer circuit
To set the current-transformer circuit, proceed as follows:
1. Go to
Settings > Parameters > Transformer data > Current-trans-
former circuit
.
2. Select the desired option.