7 Operation
Maschinenfabrik Reinhausen GmbH 2019
250
5163667/06 EN
ETOS
®
IM
Cust. limit (long-term): K
You can use this parameter to set the customer-specific limit for the maxi-
mum load factor for long-term overload of the transformer. To do so, proceed
as follows:
1. Go to
Settings > Parameters > Overload > Cust. limit (long-term): K
.
2. Enter the desired value.
3. Press the
Accept
button to save the modified parameter.
Cust. limit (short-term): Activate L
You can use this parameter to activate or deactivate the customer-specific
limit for the maximum loss-of-life per day for short-term overload of the trans-
former. To do so, proceed as follows:
1. Go to
Settings > Parameters > Overload > Cust. limit (short-term): Ac-
tivate L
.
2. Select the desired option.
3. Press the
Accept
button to save the modified parameter.
Cust. limit (long-term): Activate L
You can use this parameter to activate or deactivate the customer-specific
limit for the maximum loss-of-life per day for long-term overload of the trans-
former. To do so, proceed as follows:
1. Go to
Settings > Parameters > Overload > Cust. limit (long-term): Ac-
tivate L
.
2. Select the desired option.
3. Press the
Accept
button to save the modified parameter.
Cust. limit (short-term): Activate K
You can use this parameter to activate or deactivate the customer-specific
limit for the maximum load factor K for short-term overload of the trans-
former. To do so, proceed as follows:
1. Go to
Settings > Parameters > Overload > Cust. limit (short-term): Ac-
tivate K
.
2. Select the desired option.
3. Press the
Accept
button to save the modified parameter.
Cust. limit (long-term): Activate K
You can use this parameter to activate or deactivate the customer-specific
limit for the maximum load factor K for long-term overload of the transformer.
To do so, proceed as follows:
1. Go to
Settings > Parameters > Overload > Cust. limit (long-term): Ac-
tivate K
.
2. Select the desired option.
3. Press the
Accept
button to save the modified parameter.