5 Mounting
Maschinenfabrik Reinhausen GmbH 2019
81
5163667/06 EN
ETOS
®
IM
2. Insert and fasten the plug into the respective "24V DC" slot.
Figure 75: Fastening the 24 V DC plug
5.6.12 Wiring the QS3.241 assembly
WARNING
Risk of burns and damage to the device!
There is a fire hazard if the cables for the 24 V supply to the assemblies are
insufficiently dimensioned. This can lead to severe burns and property dam-
age.
► Only use cables with a cross-section of 1.5 mm².
The G1 (PULS) assembly is to be used exclusively for supplying the assem-
blies of this product and the cable routing is to be as short as possible (ca-
ble length: max. 2.5 m). Otherwise malfunctions may occur.