7 Operation
Maschinenfabrik Reinhausen GmbH 2019
280
5163667/06 EN
ETOS
®
IM
6. Select the desired
IED
with the configuration that is to be imported and
select
Accept
to start the import.
Figure 204: Selecting an IED
7. Upon successful completion of the import, restart the device.
ð
The system restarts and checks the configuration. If the configuration
failed, an error message appears and the device resets the configuration
to the one with which it was delivered.
7.23.7.3 Configuring GOOSE subscriber
If you configure the device as a GOOSE subscriber, you can receive
GOOSE messages from an IED in the network and link them to device func-
tions. You can use this function to display all of the device's digital input sig-
nals via GOOSE.
GOOSE datagram requirements
The data point string may contain a maximum of 52 characters. The data
point string is comprised of the following values: IED name, FCDA IdInst,
prefix, InClass, InInst, fc, doName, daName.
In order to link GOOSE datagrams of an IED with device functions, the IED
must contain a GOOSE control block (GSEControl) in the LN0 node and a
valid DataSet and GSE block. The referenced DataSet may contain data ob-
jects (DO) or data attributes (DA). The maximum number of usable data
points per GOOSE message is defined in Private Element type="MR-MAX-
GOOSE-SUBSCRIBER-FCDA". You cannot adjust this value.