9 Messages
Maschinenfabrik Reinhausen GmbH 2019
342
5163667/06 EN
ETOS
®
IM
No.
Name
Description
Remedy
Q
1
154
Invalid measured voltage
value
The measured voltage value is in-
valid.
The TAPCON® voltage measure-
ment is not working correctly.
Check the measurement trans-
former and the wiring of the corre-
sponding TAPCON®.
-
155
Circulating reactive current
calculation
Circulating reactive current can-
not be calculated.
The current-measurement system
of a TAPCON® is not working
properly. Check the measurement
transformers and the wiring of the
corresponding TAPCON®.
-
156
Motor protective switch
Motor protective switch triggered.
Follow the operating instructions
for the motor-drive unit.
-
157
Calculation of active-power
dependent desired value
The active-power dependent de-
sired value cannot be calculated.
The active power needed to cal-
culate the desired value cannot
be determined. Check the mea-
surement transformers and their
wiring.
-
158
Resistor contact series cali-
bration
The resistor contact series cali-
bration has not yet been per-
formed or has failed.
Perform the resistor contact se-
ries calibration.
-
159
Tap positions of transformers
not the same
The tap positions of the trans-
formers running in parallel are not
the same.
Check the current operating con-
ditions of the transformers.
-
176
Tap position analog input
Measured value is outside per-
missible range of analog input.
Check the signal source and
wiring of the analog input.
-
177
Desired value for analog input Measured value is outside per-
missible range of analog input.
Check the signal source and
wiring of the analog input.
-
178
Desired value for analog out-
put
The value cannot be issued via
the analog output.
Check the parameter settings and
the wiring of the analog output.
-
179
Voltage analog output
The value cannot be issued via
the analog output.
Check the parameter settings and
the wiring of the analog output.
-
180
Current analog output
The value cannot be issued via
the analog output.
Check the parameter settings and
the wiring of the analog output.
-
181
Active current analog output
The value cannot be issued via
the analog output.
Check the parameter settings and
the wiring of the analog output.
-
182
Reactive current analog out-
put
The value cannot be issued via
the analog output.
Check the parameter settings and
the wiring of the analog output.
-
183
Active power analog output
The value cannot be issued via
the analog output.
Check the parameter settings and
the wiring of the analog output.
-
184
Reactive power analog output
The value cannot be issued via
the analog output.
Check the parameter settings and
the wiring of the analog output.
-
185
Apparent power analog output The value cannot be issued via
the analog output.
Check the parameter settings and
the wiring of the analog output.
-
186
Tap position analog output
The value cannot be issued via
the analog output.
Check the parameter settings and
the wiring of the analog output.
-