7 Operation
Maschinenfabrik Reinhausen GmbH 2019
232
5163667/06 EN
ETOS
®
IM
The operation described below is only possible if you access the visualiza-
tion using a computer. You can only change the configuration of the analog
inputs and outputs if you have a Parameter Configurator or Administrator
role.
When in delivery status, you can log in as the administrator as follows:
▪ User name:
admin
▪ Password:
admin
Creating a backup
You need to create a backup to be able to reset the system in the event that
any incorrect configuration settings are made. To do so, proceed as follows:
1. Go to
Settings > Export
.
2. Go to the option
Settings
to export a backup copy of the current settings.
3. Select the desired
Interface
(USB or PC).
4. Press the
Export
button to start the export.
Configuring AIO
To configure the device's analog inputs and outputs, proceed as follows:
1. Go to
Settings > AIO configuration
.
2. Configure the properties as desired.
3. Press the
Accept
button.
4. Confirm the security prompt with
Save
to save the changes.
Also refer to
2
7.18 Configuring digital inputs and outputs
Upon delivery, the configurable digital inputs and outputs of the device are
configured as follows:
▪ Input: High active
▪ Output: Normally open contact (NO)
You can change this configuration if necessary.
If you have connected sensors over the MR sensor bus, you must select the
"Modbus" signal type for the desired functions. Observe the additional infor-
mation provided in the MR sensor bus [
Section 7.16, Page 219] section.
Ensure that the configuration of the digital inputs and outputs is suitable for
the functions used. Otherwise malfunctions may occur in the device and the
connected periphery.
The following information is displayed in tabular form for configuring the digi-
tal inputs and outputs. Grayed out elements cannot be changed.