![MR ETOS IM Operating Instructions Manual Download Page 102](http://html.mh-extra.com/html/mr/etos-im/etos-im_operating-instructions-manual_1844393102.webp)
7 Operation
Maschinenfabrik Reinhausen GmbH 2019
102
5163667/06 EN
ETOS
®
IM
Figure 89: Active power-dependent adjustment of desired voltage value
U
ref
Desired value
U
min
Minimum desired value
P
meas
Measured active power
U
max
Maximum desired value
P
min
Active power at minimum de-
sired value
U
0
Set desired value when mea-
sured active power = 0
P
max
Active power at maximum de-
sired value
Response to active power P
max
being exceeded
If the measured active power P
meas
exceeds the set parameter P
max
, the value
U
max
is adopted as the desired value.
Response to value falling below active power P
min
If the measured active power P
meas
falls below the set parameter P
min
, the
value U
min
is adopted as the desired value.