![MR ETOS IM Operating Instructions Manual Download Page 388](http://html.mh-extra.com/html/mr/etos-im/etos-im_operating-instructions-manual_1844393388.webp)
12 Technical data
Maschinenfabrik Reinhausen GmbH 2019
388
5163667/06 EN
ETOS
®
IM
Interfaces
Interface
Pin
Description
L1
NC
L2
NC
L3
N
L1
Voltage input for phase L1
NC
Not used
L2
Voltage input for phase L2
NC
Not used
L3
Voltage input for phase L3
N
Voltage input for neutral conductor
Table 129: Voltage measurement
Interface
Pin
Description
k1
l1
k2
l2
k3
l3
k1, l1,
k2, l2,
k3, l3
No function
Table 130: Current measurement
Interface
Pin
Description
1A, 1B,
1C, 2A,
2B, 2C
No function
Table 131: Relay
12.5 Digital inputs and outputs
DIO 28-15
DIO 42-20
DIO 42-20 HL
Inputs (plug-based
electrical isolation)
Quantity
28
42
Logical 0
0...10 V AC (RMS)
0...10 V DC
0...40 V AC (RMS)
0...40 V DC
Logical 1
18...260 V AC (RMS)
18...260 V DC
170...260 V AC (RMS)
170...260 V DC
Input current
Typ. 1.3 mA (regardless of
U
)
Simultaneity factor
at 70 °C and
U
≥ 230 V: max. 50 %
Summary of Contents for ETOS IM