7.1.8 Servo Ready Output
When the servo drive is powered on, if no faults are present, the Y3 output can be configured output a
“servo ready” signal.
This servo ready function can be configured via M Servo Suite software, or by changing parameter P-68
(MO) the first digit (from right to left) on the drive’s control panel.
Signal Name
PIN
P-68(MO)
Condition
Function
Y3
Y3 (42)
OUT- (41)
□□□E
Closed
Closed when servo is not ready
Open
Open when servo is ready
□□□D
(default)
Closed
Closed when servo is ready
Open
Open when servo is not ready
□□□3
(default)
General purpose, function disabled
Software Configuration
On the Drive Configuration page - Input & Output select Y5 output to set up.