M2DC Series Hardware Manual
122
Rev. 1.1
2018/04
400-820-9661
P-14 (PM)
Power-up mode
Data Range
Default
Unit
Data type
2, 5, 7,8,9,10
2
------
DEC
The power-up mode of the drive. PM determines how the drive is configured for serial communications
at power-up. For example, for SCL applications set PM=2 or PM=5. The power-up mode can also be set
when configuring the drive with Quick Tuner or ST Configurator. PM2 (Q / SCL) is the same as PM7 (Q
Program Mode), except the program is not automatically executed at power up.
P-15 (JM)
Jog mode
Data Range
Default
Unit
Data type
1, 2
2
------
DEC
There are two Jog modes available:
JM 1: Jog Mode 1 uses position control that moves the target position which causes the servo to move
at the set velocity. Jog Mode 1 will cause the servo motor to always move the same distance over time. A
drawback is that the servo can fault if the position error during the move exceeds the value set by the PF
(Position Fault) command.
JM 2: uses velocity control that applies torque to the motor to maintain velocity. This method functions
better with high inertia loads because it ignores the value set by the PF (Position Fault) command. It also
allows the drive to function in a “torque-limited velocity” mode or a “velocity-limited torque” mode. Jog
Mode 2 also uses a different set of control parameters, VI and VP, for “tuning” the velocity mode.
P-16 (GC)
Current Command of Torque
Mode
Data Range
Default
Unit
Data type
Based on drive’s output
ability
0
0.01A
DEC
The immediate current for the servo motor and drive when the servo drive is set for Command Torque
Mode.
NOTE: if you need to view or set this value on the drive’s control panel, refer to the following calculation:
LED
display
value
=
x 100
Where
is target setting current, Unit for is A (amps)
P-17 (CC)
Rated Maximum current
Data Range
Default
Unit
Data type
Depends on motor model
0.5
A
DEC
The continuous (RMS) current setting of the servo drive.
NOTE: In normal operation, please DO NOT change this parameter.
NOTE: if you need to view or set this value on the drive’s control panel, refer to the following calculation:
LED
display
value
=
x 100
Where
is target setting current, Unit for is A (amps)