M2DC Series Hardware Manual
7.1.5 Control Mode Selection
M2DC series servo drives allows to the choice of 2 types of control modes to be selected by using
external input X8. The control modes can be configured via two parameters P-12 (CM) and P-13 (CN).
In factory default mode, the control mode switch function is disabled. It can be configured via M Servo
Suite or P-65 (MI) third digit (from right to left) in parameter setting mode on the drive’s control panel.
Signal Name
PIN
P-65 (MI)
Condition
Function
X8
X8+ (12)
X8- (32)
□1□□
Closed
Use Control mode 1 - P-12 (CM)
Open
Use Control mode 2 - P-13 (CN)
□2□□
Closed
Use Control mode 2 - P-13 (CN)
Open
Use Control mode 1 - P-12 (CM)
□3□□ (Default)
Always use control mode 1 - P-12 (CM)
Software Configuration
On the Drive Configuration page - Input & Output, select X8 function to set up.