SST-PB3-REM
User Reference Guide
Explicit Messaging
189
©2014 Molex Inc.
Document Edition: 1.1.4.0, Document #: 715-0106, Template Edition: 1.1, Template #: QMS-06-045
Use, duplication or disclosure of this document or any of the information contained herein is subject to the restrictions on page ii of this document.
07h
Another command is already in progress for this slave / class 2 connection.
0Ah
Invalid remote address
0Ch
Invalid data length
0Fh
DP-V1 is not initialized
11h
Online state expected
13h
Invalid slave response
16h
No space left on command queue
9.2.3 DP-V1 Initiate Command
This command initiates a DP-V1 Class 2 connection to a slave.
Note
When using Class 2 communication only, up to 16 Class 2 connections
can be initiated.
In RSLogix5000 a MSG instruction of the CIP generic message type should be used.
Table 9.2-9: CIP Generic Message Parameters
Value
Message Parameter Name
0x64
Object
0x54
Service
1
Instance
[33..244]
Length