SST-PB3-REM
User Reference Guide
Explicit Messaging
199
©2014 Molex Inc.
Document Edition: 1.1.4.0, Document #: 715-0106, Template Edition: 1.1, Template #: QMS-06-045
Use, duplication or disclosure of this document or any of the information contained herein is subject to the restrictions on page ii of this document.
9.2.11 Basic Diagnostics
Send this explicit message to the Diagnostic Object (Basic diagnostic) to get the current state
of the SST-PB3-REM
In RSLogix5000 a MSG instruction of the CIP generic message type should be used.
Table 9.2-34: CIP Generic Message Parameters
Value
CIP Generic Message
Parameter
0x66
Object
0x01
Get Attribute All Service
1
Instance
0
Attribute
0
Length
Command Data: N/A.
Table 9.2-35: Response Data
Id Offset size Name
Description
1
0
4
dwFirmwareVersion
Firmware version
2
4
4
dwBootromVersion
Boot Rom Version
3
8
4
dwCIPSerialNumber
CIP Serial number
4
12
4
byIsConfigFilePresent
Configuration file presence
5
16
4
dwCrcIOMapping
CRC IO mapping / Reserved
6
20
4
dwCrcConfigFile;
CRC configuration file
7
24
4
dwIp
IP Address
8
28
4
dwMask
Subnet mask
9
32
4
dwGateway
Default gateway
10 36
2
wConfigFileVersion
Configuration file version
11 38
2
wEipInterface
Eip interface version
12 40
2
wSupportedConfFileVer
Supported configuration file
version
13 42
2
wComDtmConnection
Number of ComDTM
connection