SST-PB3-REM
User Reference Guide
System Overview
17
©2014 Molex Inc.
Document Edition: 1.1.4.0, Document #: 715-0106, Template Edition: 1.1, Template #: QMS-06-045
Use, duplication or disclosure of this document or any of the information contained herein is subject to the restrictions on page ii of this document.
Table 1.3-1: Exclusive Owner Connections
Assembly Type
Connection Parameter
Assembly Instance
Data Size (in Bytes)
Master 1
st
Connection –
Exclusive Owner
Input
111
500
Output
121
496
Configuration
131
8 (or 0) *
Master 2
nd
Connection –
Exclusive Owner
Input
112
500
Output
122
496
Configuration
131
0 (or 8) **
Master 3
rd
Connection –
Exclusive Owner
Input
113
500
Output
123
496
Configuration
131
0 (or 8) **
Master 4
th
Connection –
Exclusive Owner
Input
114
500
Output
124
496
Configuration
131
0 (or 8) **
Slave Connection (when also
using the Master mode)
– Exclusive Owner
Input
141
244
Output
151
244
Configuration
131
0 (or 8) **
Slave Only Connection (no
Master mode)
– Exclusive Owner
Input
142
248
Output
152
248
Configuration
132
6
Status –
Input Only
Input
161
500
Output
171
0
(*): 0 if no configuration data is used.
(**): By default this value should be left at 0. If set to 8, configuration data must match
configuration data from the first Exclusive Owner connection.
Listen-only connection refers to a connection that is made to an SST-PB3-REM module that is
already configured with an Exclusive Owner connection from the main controller. A Listen-only
connection allows inputs on an SST-PB3-REM module to be monitored from another controller.
Up to 5 Exclusive Owner connections may be configured on the module. For each Exclusive
Owner connection one Listen-only connection may also be configured, as seen in Table 2.3-2:
Listen-only Connections.
When setting up a listen-only connection in RSLogix5000 the data format must be identical with
the data format that is configured on the controller with the Exclusive Owner connection.
Supported data formats for listen-only are:
•
Input Data SINT - With Status.