User Reference Guide
SST-PB3-REM
106
Configuring and Programming the DP Master
©2014 Molex Inc.
Document Edition: 1.1.4.0, Document #: 715-0106, Template Edition: 1.1, Template #: QMS-06-045
Use, duplication or disclosure of this document or any of the information contained herein is subject to the restrictions on page ii of this document.
5.3 Registering SST-PB3-REM EDS file
The following steps were done using Rockwell’s Studio 5000 Version 21 and RSlinx
version 3.51 .To use the EDS AOP for the SST-PB3-REM Remote Module, Studio 5000
Version 21 or higher is required.
With Studio 5000 there are two ways to register the EDS file. If you have the SST-PB3-
REM connected to your Ethernet network and it's shown under the Ethernet/IP driver in
RSlinx as below then the EDS file can be uploaded from module into RSlinx. The other
way to register the EDS file is to use Rockwell's EDS hardware Installation Tool. This
tool can be used when browsing for the SST-PB3-REM on the Ethernet network is not
possible.
5.3.1 Registering EDS file via Upload EDS file from device using
RSLinx
1.
Launch RSlinx
2.
Enable Autobrowse if not already selected.
3.
Highlight and Right-Click on SST-PB3-REM.
4.
Select Upload EDS file from device.