Configuring and Programming the DP Master
©2014 Molex Inc.
Document Edition: 1.1.4.0, Document #: 715-0106, Template Edition: 1.1, Template #: QMS-06-045
Use, duplication or disclosure of this document or any of the information contained herein is subject to the restrictions on page ii of this document.
5.8 PLC Connection Error Codes
Name
CIP
Error
Description
CRC_PERMISSION_DENIED
0x0F
IO CRC does not match
NOT_IN_MASTER_STATE
0x10
Not in master state (no configuration
file in flash)
NOT_IN_SLAVE_STATE
0x10
Not in slave state (configuration file
present in flash)
CNX_OUT_OF_SEQ
0x0C The module received a connection
request without before opening the first
connection (111/121/131)
BAD_PARAM_AUTORUN
0x09
Invalid parameter for Autorun flag (0 or
1 are valid)
BAD_PARAM_SLV_INPUT
0x09
Slave input length to long (over 244)
BAD_PARAM_SLV_OUTPUT
0x09
Slave output length to long (over 244)
BAD_PARAM_SLV_STN_NUM 0x09
Slave station number to high (over
125)
BAD_PARAM_SLV_BAUD
0x09
Baud rate invalid (0 – 11 are valid)
BAD_PARAM_SWAP_WORD
0x09
Invalid parameter for swap word flag (0
or 1 are valid)