User Reference Guide
SST-PB3-REM
32
Hardware Features
©2014 Molex Inc.
Document Edition: 1.1.4.0, Document #: 715-0106, Template Edition: 1.1, Template #: QMS-06-045
Use, duplication or disclosure of this document or any of the information contained herein is subject to the restrictions on page ii of this document.
-
General network errors – occur when
there are problems on the network but
not severe enough to cause a network
timeout error.
-
Duplicate station errors – occur when a
duplicate station is detected.
-
Pass token errors – occur when the
module is unable to pass the token.
Usually caused by bad wiring (shorted)
or other hardware problems.
Off
Communication with all the devices in the scan
list is OK, there are no network errors, or the
module is offline on the Profibus network.
Solid Red
Duplicate active station address detected.
PFB STATE (Profibus State)
LED State
Description/Meaning
Solid Yellow
Profibus Stop Mode.
Flashing Yellow Slave Only Mode – the module is being scanned
in Clear or Operate mode by a DP Master.
Flashing Green
Profibus Clear Mode.
Solid Green
Profibus Operate Mode.
Off
Profibus Offline Mode.
PLC RUN/PROG
LED State
Description/Meaning
Off
PLC is off – there is no EtherNet/IP connection
between the module and PLC.
Flashing Yellow PLC is in PROG mode – EtherNet/IP
connections are in idle state.
Solid Yellow
PLC is RUN mode.