The ErrStn Counter
This register increments when a duplicate station is detected. If this error occurs when the SST-
PB3-REM is going online, the module increments the errStn counter and stays offline.
The ErrPasTok Counter
This register increments when the SST-PB3-REM is unable to pass the token. This is usually
caused by bad wiring (shorted) or other hardware problems. The module tries to pass the token,
fails to hear its own token pass message, and puts itself offline.
The ErrLasBad Counter
This register increments when the active station list on the ASPC2 LAN controller is invalid
because of multiple network errors. This error is caused by bad wiring or hardware.