Basic Function Blocks
48
10/00 AWB27-1301-GB
Parameter assignment
The basic function block TCMT2_BS is assigned with the
following parameters:
CAL FW_TLBP(
reset:=,
Resets the function block
strobe:=,
If the “strobe” input has been assigned the constant
value “1”, the exchange of data starts automatically
when the controller is switched on
fixed_length:=8,
User data length for fixed length frames
baudrate:=1200,
Transmission speed
slotnumber:=4,
Slot address of the PS416-TCS-200
address_of_station_1:=1,
Address of station 1
address_of_station_2:=2,
Address of station 2
address_of_station_3:=0,
Address of station 3 (not available)
address_of_station_n:=0,
Address of station n (not available)
tra_dat:=
Send data array
|
:=active,
Indicates that a service is being processed.
:=active_cyclic,
Indicates that a polling cycle is in progress.
:=result,
Result becomes active after a falling edge at the
output. Result = 0: Error, Result = 1: OK
:=dcd,
Signal quality evaluation
:=fail,
Error indication at a station after a frame was repeated
n times
:=fail_stationaddress,
Address of the secondary station at which an error has
occurred after a frame was repeated n times.
:=fail_code,
Error code if “result” = 0
:=life_control,
Life control bits
:=user_status,
Array of user status bits
:=actual_stationaddress,
Active station address
:=rec_dat)
Receive data array
Summary of Contents for S40-AM-TL
Page 7: ...10 00 AWB27 1301 GB 4 ...
Page 9: ...6 10 00 AWB27 1301 GB ...
Page 13: ...10 10 00 AWB27 1301 GB ...
Page 55: ...Basic Function Blocks 52 10 00 AWB27 1301 GB ...
Page 103: ...100 10 00 AWB27 1301 GB ...
Page 107: ...104 10 00 AWB27 1301 GB ...
Page 113: ...10 00 AWB27 1301 GB 110 ...