39
10/00 AWB27-1301-GB
4 Basic Function Blocks
The basic function blocks give the user access to service 17
(send/read data of fixed frame length RAM), and poll all the
programmed stations in a continuous cycle. The basic
function blocks are permanently programmed:
• Frame format: FT3
• Frame repeated in the event of an error: 3
Interface
The basic function blocks have the following inputs and
outputs depending on the station type:
Table 8:
User interface of the function block
Inputs/outputs
Basic function block
Primary
station
Secondary
station
Inputs
reset
x
x
strobe
x
–
local_stationaddress
–
x
baudrate
x
x
watchdog_time
–
x
fixed_length
x
x
slotnumber
(with TCMTx-xS)
x
x
address_of_station_1
x
–
address_of_station_n
x
–
tra_dat
x
x
TCM_tdata
(with TCMTx-xT)
x
x
TCM_rdata
(with TCMTx-xT)
x
x