Organisation
13
10/00 AWB27-1301-GB
Subaddress:
Specifies the number of available offset address ranges (for
universal function blocks only).
Offset address:
Specifies the maximum number of bytes in a subaddress.
The maximum data array size that can be defined in the
primary station is approximately 7.5 Kbyte for the send and
receive data arrays. This available range must be distributed
equally between all the secondary stations in the telecontrol
line. The maximum data array size of each secondary station
is thus 7680 bytes divided by the number of secondary
stations in the telecontrol line.
Always ensure that you do not exceed the maximum data
range size when specifying offset addresses and
subaddresses.
Many different combinations of subaddresses and offset
addresses are possible. Some examples are given in the
following table.
Table 3:
Specimen combinations for setting up data arrays with
8 secondary stations
Offset addresses
⫻
subaddresses
F
maximum data array range
size
Subaddresses
[
byte
]
Offset address
[
byte]
Data array
size
[
byte]
256
3
768
4
220
880
15
64
960
20
48
960
10
30
300
18
50
900
Summary of Contents for S40-AM-TL