Secondary station
99
10/00 AWB27-1301-GB
4F
79
PLC NOT RUN
The CPU at the secondary station is not in “RUN” mode. Check the operating mode
selector switch or the diagnostic LEDs of the CPU.
7F
127
Communication error
Data was received that cannot be interpreted by the station.
Check whether
– all the stations are set to the same baud rate,
– two stations have the same station address,
– there is a fault on one of the transmission lines,
– the modems are working correctly.
– synchronous mode was programmed on the modules.
Error code
Description
hex
dec