Installation
33
10/00 AWB27-1301-GB
Constant parameter blocks
A constant block is provided for every parameter function
block. The function block is adapted to the required function
by changing the parameters.
TCMT2_BS
cts_gap_time (TIME)
for the ZB4501-TC1/
-TC2 modules
This time has two functions:
– The monitoring the CTS signal line
Requirement: RTS = 1
If no CTS signal is detected after this time, the send operation is
aborted with “fail_code” = 14.
If the time value = 0, the CTS timeout time is set internally to
500 ms.
– The masking of gaps in receive frames.
This is only necessary when wireless modems are used. For this a
value of 50 ms must be set.
tel_repeat:
Number of frames repeated in the event of a protocol error.
(only with basic primary stations, otherwise as input)
VAR CONSTANT
dfn_max
: UINT:=32;
(*Number of secondary stations*)
tra_dfl_max
: UINT:=20;
(*Transmit length of data array*)
rec_dfl_max
: UINT:=20;
(*Receive length of data array*)
system_time
: TIME:=T#500ms;
(*System time*)
repeat_time
: TIME:=T#50ms;
(*repeat time after job end*)
start_delay
: TIME:=T#2000ms;
(*Start delay with autostart*)
rts_delay_on
: TIME:=T#10ms;
(*RTS on-delay*)
rts_delay_off
: TIME:=T#30ms;
(*RTS off-delay*)
cts_time
: TIME:=T#500ms;
(*CTS timeout*)
tel_repeat
: USINT:=3;
(*Frame repeated in the event of an
error*)
END_VAR
Summary of Contents for S40-AM-TL
Page 7: ...10 00 AWB27 1301 GB 4 ...
Page 9: ...6 10 00 AWB27 1301 GB ...
Page 13: ...10 10 00 AWB27 1301 GB ...
Page 55: ...Basic Function Blocks 52 10 00 AWB27 1301 GB ...
Page 103: ...100 10 00 AWB27 1301 GB ...
Page 107: ...104 10 00 AWB27 1301 GB ...
Page 113: ...10 00 AWB27 1301 GB 110 ...