Programming the control
signal terminals
01/02 AWB8230-1415GB
92
Actuation of the contactors consists of the following steps:
• The startup takes place through the K2M bypass contactor.
• Once the motor has accelerated, switch the K2M bypass
contactor off and, with a delay (of 0.5 to 1.0 s), activate the
K3M motor contactor.
• Then, switch the K1M mains contactor on and, at the same
time, activate the digital input configured as CS.
• When the CS input is deactivated, the waiting time set under
PNU b003 begins.
• Once this time has expired, the DV6 frequency inverter synchro-
nizes to the motor speed and continues to run the motor.
X
Program one of the digital inputs 1 to 8 as CS by entering the
value 14 under the corresponding PNU (C001 to C008).
Figure 82:
Digital input configured FW as FWD (start/stop clockwise
operation) and 3 as CS (heavy mains starting)
CS
FWD
P24
FW
3
Figure 83:
Function chart for CS (heavy mains starting)
CS
FW
PNU b003
0.5 – 1.0 s
K3M
K2M
K1M
f
o
f
20 ms
f
0.5 s
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
b003
Waiting time
before restart
–
j
0.3 to 100 s
Here, set a time which is to expire before an automatic
restart is initiated after the supply voltage is connected. This
time can also be used in conjunction with the FRS function.
During the delay, the following message appears on the LED
display:
1.0