Programming the control
signal terminals
01/02 AWB8230-1415GB
66
Programmable digital inputs 1 to 8
Various functions can be assigned to terminals 1 to 8. Depending
on your requirements, you can configure these terminals as
follows:
• anticlockwise start signal (REV),
• selection inputs for various fixed frequencies (FF1 to FF4),
• reset input (RST),
• etc.
The terminal functions for programmable digital inputs 1 to 8 are
configured with PNU C001 to C008, i.e. with PNU C001, you
specify the function of digital input 1, with PNU C002 the function
for digital input 2, etc. Note, however, that you cannot assign the
same function to two inputs at the same time.
Programmable digital inputs 1 to 8 are configured by default as
make contacts. If, therefore, you want to activate the function of
an input terminal, you must close the corresponding input (i.e.
connect the input terminal to terminal P24). Conversely, to deac-
tivate the input terminal, the input must be opened.
Table 10:
Digital inputs 1 to 8
For a detailed description of the input functions, see the pages
listed in Table 11.
Table 11:
Functions of the digital inputs
Caution!
If an EEPROM error occurs (fault message
E 008
), all
parameters must be checked to ensure that they are
correct (particularly the RST input).
PNU
Terminal
Adjustable in RUN
mode
Value
WE
Normal
Extend
ed
C001
1
–
j
a
Table 11
18
C002
2
16
C003
3
06
C004
4
11
C005
5
09
C006
6
03
C007
7
02
C008
8
01
Value
Function
Description
a
Page
01
REV
Start/stop anticlockwise
operation
68
02
FF1
First fixed frequency input
69
03
FF2
Second fixed frequency input
04
FF3
Third fixed frequency input
05
FF4
Fourth fixed frequency input
06
JOG
Jog mode
79
07
DB
DC braking
88
08
SET
Selection of the second
parameter set
86
09
2CH
Second acceleration and
deceleration time
74
11
FRS
Motor shutdown and free run
stop (coasting)
75
12
EXT
External fault
76
13
USP
Unattended start protection
77
14
CS
Heavy starting duty
91
15
SFT
Parameter protection
83
16
AT
Setpoint definition through
current signal
73
17
SET3
Third parameter set
86
18
RST
Reset
78
20
STA
Pulse start (3-wire)
96
21
STP
Pulse stop (3-wire)
96
22
F/R
Direction of rotation (3-wire)
96
23
PID
Activation of PID control
–
24
PIDC
Reset integral component
–
26
CAS
Motor parameter changeover
–
27
UP
Acceleration
(motor potentiometer)
84
28
DWN
Deceleration
(motor potentiometer)
84
29
UDC
Reset frequency
(motor potentiometer)
84
31
OPE
Setpoint value through keypad
93
32
SF1
Bitwise frequency selection
71
33
SF2
34
SF3
35
SF4
36
SF5
37
SF6
38
SF7
39
OLR
Current limit switch over
90