![Moeller DV6-340 Series Manual Download Page 48](http://html.mh-extra.com/html/moeller/dv6-340-series/dv6-340-series_manual_1819311048.webp)
01/02 AWB8230-1415GB
45
4 Operating the DV6
This section describes how to take the DV6 frequency inverter into
operation and what you should observe during its operation.
Initial startup
Observe the following points before you take the frequency
inverter into operation:
• Make sure that the power lines L1, L2 and L3 and the frequency
inverter outputs U, V and W are connected correctly.
• The control lines must be connected correctly.
• The earth terminal must be connected correctly.
• Only the terminals marked as earthing terminals must be
earthed.
• The frequency inverter must be installed vertically on a non-
flammable surface (e.g. a metal surface).
• Remove any residue from wiring operations – such as pieces of
wire – and all tools from the vicinity of the frequency inverter.
• Make sure that the cables connected to the output terminals are
not short-circuited or connected to earth.
• Ensure that all terminal screws have been sufficiently tightened.
• Make sure that the frequency inverter and the motor are correct
for the mains voltage.
• The configured maximum frequency must match the maximum
operating frequency of the connected motor.
• Never operate the frequency inverter with opened power
section covers.
The control signal terminals are wired as follows.
X
Switch on the supply voltage.
The POWER and Hz LEDs light up (keypad). The display should
indicate
0.0.0
.
X
Close switch S1 (FW = clockwise operation).
X
With potentiometer R1, you can set the frequency and therefore
the motor speed.
The motor turns clockwise and the display indicates the set
frequency.
X
Open switch S1.
The motor speed is reduced to zero (display:
0.00
).
X
Close switch S2 (REV = anticlockwise operation).
X
With potentiometer R1, you can set the frequency and therefore
the motor speed.
The motor turns anticlockwise and the display indicates the set
frequency.
X
Open switch S2.
The motor speed is reduced to zero (display:
0.00
).
If both switches S1 and S2 are closed, the motor will not start. If
you close both switches during operation, the motor speed is
reduced to zero.
If a fault has occurred due to overcurrent or overvoltage, increase
the acceleration or deceleration time (
a
Section “Acceleration
time 1“, Page 121 and Section “Deceleration time 1“, Page 122).
By default, the ON key and the potentiometer on the keypad
(
a
Fig. 40 and
a
Table 7) have no assigned function. For
details about activating these devices,
a
Section “Setting the
frequency and start signal parameters“, Page 123.
Caution!
Do not carry out h.v. tests. Built-in overvoltage filters are
fitted between the mains voltage terminals and earth,
which could be destroyed.
h
Sparkover voltage and insulation resistance tests (megger
tests) have been carried out by the manufacturer.
Figure 39:
Connecting the control signal terminals (default settings)
8
L
S2
4K7
M
REV
R1
S1
O
H
F
20 m
FW P24
PES
M
FWD
Caution!
During or after intitial operation, check the following
points to prevent damage to the motor:
• Was the direction of rotation correct?
• Has a fault occurred during acceleration or decelera-
tion?
• Was the frequency displayed correctly?
• Did any unusual motor noise or vibration occur?
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616