Appendix
01/02 AWB8230-1415GB
188
Ambient conditions
Ambient temperature
–10 to +50 °C
From about +40 to +50 °C, the pulse frequency should be reduced to 2 kHz. The output current should be
less than 80 % of the rated current in this case.
Temperature/humidity during storage
–25 to 70 °C (for short periods only, e.g. during transport)
20 to 90 % relative humidity (non condensing)
Permissible vibration
Maximum 5.9 m/s
2
(= 0.6 g) at 10 to 55 Hz
Installation height and location
Maximum 1000 m above sea level in a housing or control panel (IP54 or similar)
Optional accessories
• Remote operating unit: DEX-KEY-10
• Choke to improve the power factor
• DE6-LZ...-V4 RFI filter
• Expansion modules
– Encoder module: DE6-IOM-ENC
– PROFIBUS-DP module: DE6-NET-DP
DV6-340-...
075
1K5
2K2
4K0
5K5
7K5
11K
15K
18K5
DV6-340-...
22K
30K
37K
45K
55K
75K
90K
110K
132K
Protection class accor-
ding to EN 60529
IP20
Overvoltage category
III
Maximum permissible effective motor
power in kW, details for four pole three-
phase current asynchronous motors
22.0
30.0
37.0
45.0
55.0
75.0
90.0
110
132
Maximum permissible
apparent motor power
in kVA at
400 V
33.2
40.1
51.9
62.3
76.2
103.2
121.9
150.3
180.1
480 V
39.9
48.2
62.3
74.8
91.4
123.8
146.3
180.4
216.1
Primary side: Number of phases
Three-phase
Primary side: Rated voltage
342 V ~ – 0 % to 528 V ~ + 0 %, 47 to 63 Hz
Secondary side: Rated voltage
Three-phase 380 to 480 V ~
Corresponding to the primary side rated voltage
If the primary voltage drops, the secondary voltage also drops.
Primary side: Rated current in A
53.0
63.0
83.0
99.0
121
164
194
239
286
Secondary side: Rated current in A
48.0
58.0
75.0
90.0
110
149
176
217
260
Secondary side: Frequency range
0.1 to 400 Hz
With motors which are operated at rated frequencies above 50/60 Hz, the maximum possible motor speed
should be observed.
Frequency error limits (at 25 °C
g
10 °C)
• Digital setpoint value:
g
0.01 % of the maximum frequency
• Analog setpoint value:
g
0.2 % of the maximum frequency
Frequency resolution
• Digital setpoint value: 0.1 Hz
• Analog setpoint value: Maximum frequency/1000
Voltage/frequency characteristic
• Constant torque
• Reduced torque
• Increased (SLV-controlled) torque
• Vector-controlled torque (only with optional DE6-IOM-ENC module)
• User-programmable
V
/
f
characteristic
Permissible overcurrent
150 % for 60 s, 200 % for 0.5 s (once every ten minutes)
Acceleration/deceleration time
0.01 to 3600 s with linear and nonlinear characteristic (applies also for second and third acceleration/
deceleration time)
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616