Programming the control
signal terminals
01/02 AWB8230-1415GB
64
Matching analog input OI
Figure 51 shows the matching possibilities for the 4 to 20 mA
setpoint current. PNU A103 and A104 specify the active current
range. In PNU A101, you can set the starting point, and in
PNU A102 the end point for the output frequency. If the line does
not start at the origin, (PNU A101 and A103 > 0), the starting
frequency with PNU A105. As long as the input signal is smaller
than the value entered under PNU A103, either 0 Hz (for
PNU A105 = 00) or PNU A101 (for PNU A105 = 01) is output.
Figure 51:
Setpoint current, terminals OI-L
PNU A101
4 mA
PNU A103
PNU A104
20 mA
0 %
100 %
PNU A102
PNU A004
PNU A105 = 0
PNU A105 = 1
f
[Hz]
I
OI-L
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
A101
Starting
frequency,
input OI
–
j
0.00 to
400 Hz
Here, you define the starting frequency for the minimum
setpoint current (PNU A103).
0.00
A102
End frequency,
input OI
–
j
0.00 to
400 Hz
Here, you define the end frequency for the maximum
setpoint current (PNU A104).
0.00
A103
Minimum
current
setpoint,
input OI
–
j
0 to 100 %
Minimum setpoint value as a percentage of the highest
possible current (20 mA).
20
A104
Maximum
setpoint
current, input OI
–
j
0 to 100 %
Minimum setpoint value as a percentage of the highest
possible setpoint current (20 mA).
100
A105
Condition for
starting
frequency for
analog input OI
–
j
Determines the behaviour at setpoint values below the minimum setpoint
value.
01
00
The frequency defined under PNU A101 is applied to the
motor.
01
A frequency of 0 Hz is applied to the motor.