Programming the control
signal terminals
01/02 AWB8230-1415GB
104
Run signal (RUN)
The digital output configured as RUN remains activated as long as
a frequency not equal to 0 Hz is present, i.e. as long as the motor
is driven in a clockwise or anticlockwise direction. The RUN signal
is also active during DC braking.
X
Program one of the digital outputs 11 to 15 as RUN output by
setting the value 00 in the corresponding PNU (C021 to C025)
or in PNU C026 for signalling relay contacts K11-K12.
By default, RUN is assigned to digital output 12.
Figure 103: Digital output 11 configured as RUN (Run signal)
Figure 104: Function chart for RUN (Run signal)
f
o
: Output frequency
a
At PNU b082 set starting frequency
RUN
24 V
50 mA
11
CM2
12
13
14
15
–
+
FWD/REV
RUN
f
O
a
a
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
b082
Increased star-
ting frequency
–
j
0.5 to 9.9 Hz
A higher starting frequency results in shorter acceleration
and deceleration times (for example to overcome high fric-
tional resistance). If the frequency is too high, fault message
E02 may be issued. Up to the set starting frequency, the
motor starts without a ramp function.
0.5