![Moeller DV6-340 Series Manual Download Page 195](http://html.mh-extra.com/html/moeller/dv6-340-series/dv6-340-series_manual_1819311195.webp)
Appendix
01/02 AWB8230-1415GB
192
Ambient conditions
Ambient temperature
–10 to +50 °C
From about +40 to +50 °C, the pulse frequency should be reduced to 2 kHz. The output current should be
less than 80 % of the rated current in this case.
Temperature/humidity during storage
–25 to 70 °C (for short periods only, e.g. during transport)
20 to 90 % relative humidity (non condensing)
Permissible vibration
Up to 5.9 m/s
2
(= 0.6 g) at
10 to 55 Hz
Up to 2.94 m/s
2
(= 0.3 g) at 10 to 55 Hz
Installation height and location
Maximum 1000 m above sea level in a housing or control panel (IP54 or similar)
Optional accessories
• Remote operating unit: DEX-KEY-10
• Choke to improve the power factor
• DE6-LZ...-V4 RFI filter
• Expansion modules
– Encoder module: DE6-IOM-ENC
– PROFIBUS-DP module: DE6-NET-DP
DV6-340-...
22K
30K
37K
45K
55K
75K
90K
110K
132K
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616