Programming the control
signal terminals
01/02 AWB8230-1415GB
56
Programmable digital outputs 11 to 15
RUN
00
RUN signal
The RUN signal is output during operation of the motor.
Connection of a signal
relay to a digital output
11 to 15:
Transistor output
(open collector)
(maximum 27 V
H
, 50 mA)
FA1
01
Signal when frequency is
reached
f
s
= setpoint frequency
FA2
02
Signal when frequency is
exceeded (1)
If a digital output is configured as FA1, a signal is issued as long as
the setpoint value is reached. If a digital signal is configured as FA2,
a signal is output as long as the frequencies defined under PNU C042
and PNU C043 are exceeded.
OL
03
Signal on overload
The OL signal is output when the overload alarm threshold (adjus-
table under PNU C041) is exceeded.
OD
04
Signal on PID control
deviation
The OD signal is output when the PID control deviation set under
PNU C044 is exceeded.
AL
05
Signal (alarm) on fault
The AL signal is issued when a fault occurs.
FA3
06
Frequency reached (1)
The FA3 signal is issued when the output frequency lies in the
frequency range defined under PNU C042 and C043 (plus tolerance).
OTQ
7
Torque reached
(exceeded)
The OTQ signal is output when the set torque is reached or exceed.
IP
8
Mains failure, immediate
stop
The IP signal is issued on intermittent mains failure.
UV
9
Undervoltage signal
The UV signal is output on undervoltage.
TRQ
10
Torque limitation
The TRQ signal is output when the torque limits set under PNU b041
to b044 are reached.
RNT
11
Running time exceeded
The RNT signal is output when the running time set under PNU b034
is exceeded.
ONT
12
Mains On time exceeded
The ONT signal is output when the running time set under PNU b034
is exceeded.
THM
13
Motor thermal overload
The THM signal is output when the motor overload warning thres-
hold set under PNU C061 is exceeded.
BRK
19
Enable signal for
external brake
The BRK signal is output to enable an external brake; adjustable
under PNU b120 to b126.
BER
20
Brake fault
The BER signal is output when the BOK input of the external brake is
not deactivated; adjustable under PNU b120 to b126.
ZS
21
Zero speed
The ZS signal is output when the motor is at rest (zero speed).
DSE
22
Speed deviation
exceeded
The DSE signal is output when the deviation of the actual speed from
the setpoint value is greater than specified under PNU P027 (only
with optional DE6-IOM-ENC module).
POK
23
Positioning
The POK signal is output when positioning has been completed (only
with optional DE6-IOM-ENC module).
Name
Value
1)
Function
Description
24 V
50 mA
12
CM2
FA1
f
s
FA2
f
2
f
1