Operating the DV6
01/02 AWB8230-1415GB
48
Changing display and Basic parameters
Press the PRG key to switch from display or RUN mode to
programming mode. The PRG lamp lights up in this mode.
You can access the individual parameters or parameter groups
with the UP and DOWN arrow keys (
a
Fig. 41).
To access the programming mode, press the PRG key. You can
modify the parameter values with the arrow keys.
Exceptions are the display parameters PNU d001 to d090. These
parameters have no values. After you have selected a display para-
meter with the arrow keys, you can return to the display mode with
the PRG key. The display then shows the selected display para-
meter (
a
Section “Setting the display parameters“, Page 120).
Parameter values can be accepted with the ENTER key or rejected
with the PRG key.
To return to the display mode, press the PRG key in the display
parameter range PNU d001 to d090.
Example for changing acceleration time 1: PNU F002
The frequency inverter is in display mode and the RUN lamp is lit.
X
Press the PRG key.
The frequency inverter changes to the programming mode, the
PRG lamp lights up and
d001
or the most recently modified para-
meter appears on the display.
X
Press the DOWN key until
F002
appears on the display.
X
Press the PRG key.
The set acceleration time 1 in seconds appears on the display
(default value: 30.00).
X
To change the set value, use the UP and DOWN arrow keys.
There are now two possibilities:
X
Accept the displayed value by pressing the ENTER key.
X
Reject the displayed value by pressing the PRG key.
The display shows
F002
.
X
Press the UP key until
d001
appears.
X
Press the PRG key.
The frequency inverter changes to the display mode and displays
the set frequency.
Changing the parameters of the extended parameter
groups
The following example illustrates how to change PNU A03 of the
extended parameter group A. You can also change the parameter
values of groups B, C, H, P and U as described in the example. For
a detailed description of the extended parameter groups, see from
Section “Setting the frequency and start signal parameters“,
Page 123.
Example for changing the base frequency PNU A003
X
Press the PRG key to change to the programing mode.
The most recently modified parameter appears on the display and
the PRG lamp lights up.
X
Press the UP or DOWN key until the extended parameter group
A---
appears on the display.
X
Press the PRG key.
A001
appears on the display.
X
Press the UP key twice until
A003
appears on the display.
X
Press the PRG key.
The display shows the value entered under PNU A003
(default: 50.).
X
To change the value, use the UP and DOWN arrow keys.
There are now two possibilities:
X
Accept the displayed value by pressing the ENTER key.
X
Reject the displayed value by pressing the PRG key.
Figure 42:
Change acceleration time 1
a
Display dependent on the selected display parameter PNU d001 to
d090
b
Display of the most recently changed parameter
a
b
F02 = 29.99
F02 = 30.00
PRG
PRG
PRG
PRG
ENTER