Setting Parameters
01/02 AWB8230-1415GB
128
SLV and 0 Hz SLV control
With SLV and 0 Hz SLV control, you can achieve a high torque
output and speed stability. For a detailed description of SLV
control,
a
Section “SLV and autotuning“, Page 171.
Vector control with optional DE6-IOM-ENC module
If you are using a DE6-IOM-ENC feedback (encoder) module and
want to use it to regulate the motor torque, set PNU A044 to 05.
For a detailed description of, see manual AWB8240-1416... for the
encoder module.
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
A044
A244
A344
Voltage/
frequency
characteristic
–
–
00
Linear V/
f
characteristic (constant torque).
00
01
Quadratic V/
f
characteristic (reduced torque)
02
User-definable
03
Sensorless vector control (SLV)
1)
is active
04
0 Hz SLV
1)
is active
05
Vector control
1)
with optional DE6-IOM-ENC module
A045
Output voltage
j
j
20 to 100 %
of the input
voltage
The output voltage
can be set from 20
to 100 % of the
input voltage.
100
b100
Frequency
coordinate
f
1
–
–
0 to 400 Hz
First frequency coordinate of the
V
/
f
characteristic
3)
0
b101
Voltage coordi-
nate
V
1o
–
–
0 to
V
1
2)
or
PNU A082
First voltage coordinate of the
V
/
f
characteristic
3)
0.0
b102
Frequency
coordinate
f
2
–
–
0 to 400 Hz
Second frequency coordinate of the
V
/
f
characteristic
3)
0
b103
Voltage coordi-
nate
V
2o
–
–
0 to
V
1
2)
or
PNU A082
Second voltage coordinate of the
V
/
f
characteristic
3)
0.0
b104
Frequency
coordinate
f
3
–
–
0 to 400 Hz
Third frequency coordinate of the
V
/
f
characteristic
3)
0
b105
Voltage coordi-
nate
V
3o
–
–
0 to
V
1
2)
or
PNU A082
Third voltage coordinate of the
V
/
f
characteristic
3)
0.0
b106
Frequency
coordinate
f
4
–
–
0 to 400 Hz
Fourth frequency coordinate of the
V
/
f
characteristic
3)
0
b107
Voltage coordi-
nate
V
4o
–
–
0 to
V
1
2)
or
PNU A082
Fourth voltage coordinate of the
V
/
f
characteristic
3)
0.0
b108
Frequency
coordinate
f
5
–
–
0 to 400 Hz
Fifth frequency coordinate of the
V
/
f
characteristic
3)
0
b109
Voltage coordi-
nate
V
5o
–
–
0 to
V
1
2)
or
PNU A082
Fifth voltage coordinate of the
V
/
f
characteristic
3)
0.0
b110
Frequency
coordinate
f
6
–
–
0 to 400 Hz
Sixth frequency coordinate of the
V
/
f
characteristic
3)
0
b111
Voltage coordi-
nate
V
6o
–
–
0 to
V
1
2)
or
PNU A082
Sixth voltage coordinate of the
V
/
f
characteristic
3)
0.0
b112
Frequency
coordinate
f
7
–
–
0 to 400 Hz
Sevenths frequency coordinate of the
V
/
f
characteristic
3)
0
0
100
50
[%]
U
f
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616