![Moeller DV6-340 Series Manual Download Page 159](http://html.mh-extra.com/html/moeller/dv6-340-series/dv6-340-series_manual_1819311159.webp)
Setting Parameters
01/02 AWB8230-1415GB
156
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
b012
b212
b312
Tripping current
for electronic
motor protec-
tion device
–
j
0.2 to 1.2
x
I
e
1)
Setting range of the tripping current as a multiple of the
frequency inverter rated current, i.e. the range is given in
amperes (A).
I
e
1)
b013
b213
b313
Characteristic for
electronic motor
protection device
–
j
The electronic thermal protection of the motor in the low speed range can be
increased to improve thermal monitoring of the motor at low frequencies.
01
00
Enhanced motor protection
01
Normal overload protection
02
Adjustable under b015 to b020
b015
Frequency 1
–
j
0.0 to 400 Hz
Frequency 1 for electronic motor protection device
0
b016
Tripping
current 1
–
j
0.0 to
1000 A
Tripping current 1 for electronic motor protection device
0.0
b017
Frequency 2
–
j
0.0 to 400 Hz
Frequency 2 for electronic motor protection device
0
b018
Tripping
current 2
–
j
0.0 to
1000 A
Tripping current 2 for electronic motor protection device
0.0
b019
Frequency 3
–
j
0.0 to 400 Hz
Frequency 3 for electronic motor protection device
0
b020
Tripping
current 3
–
j
0.0 to
1000 A
Tripping current 3 for electronic motor protection device
0.0
1) Inverter rated current
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616