![Moeller DV6-340 Series Manual Download Page 123](http://html.mh-extra.com/html/moeller/dv6-340-series/dv6-340-series_manual_1819311123.webp)
Setting Parameters
01/02 AWB8230-1415GB
120
Setting the display parameters
This section describes the parameters with which you can set the
display of the LCD keypad.
PNU
Name
Function
d001
Output frequency in Hz
Output frequency display from 0.5 to 360 Hz. The “Hz” lamp on the keypad lights up.
d002
Motor current in A
Indication of the output current from 0.01 to 999.9 A (filtered indication with a time constant of
100 ms). The “A” lamp on the keypad lights up.
d003
Direction of rotation
Display:
•
F
for clockwise operation (forward),
•
r
for anticlockwise operation (reverse),
•
0
for stop
d004
Actual value
x
factor
Only with active PID control. The factor is set under PNU A075 and can have a value from 0.01 to
99.99; the default setting is 1.0.
d005
Status of digital inputs 1 to 8
Example: Digital inputs 1, 3, 5 and 7 are activated. Digital inputs2, 4, 6 and 8
are deactivated.
d006
State of digital outputs 11 to 15
and fault signal output
Example: Digital outputs 11, 13 and 15 are activated. Digital outputs 12 and
14, and signal output K14 are deactivated.
d007
Output frequency
x
factor
Indication of the product of the factor (PNU b086) and the output frequency in the range 0.01 to
99990.
Examples:
• Display indication
11.11
corresponds to 11.11,
•
111.1
corresponds to 111.1,
•
1111.
corresponds to 1111,
•
1111
corresponds to 11110.
d012
Motor torque
d013
Output voltage
0 to 600 V
d014
Electrical input power
0.0 to 999.9 kW
d016
Running time
0 to 999, in 1000 h/unit
d017
Power on time
0 to 999 h, 1000 to 9999 h (100 to 999 kh)
d080
Total fault count
d081
First (most recent) fault
Display of the most recent fault message and (after the PRG key is pressed) the output frequency,
motor current and DC bus voltage at the time the fault occurred. If there is no current fault message,
the display shows
---
d082
Second fault
Display of second from last fault message. If neither the second from last or third from last fault
message has been saved, the display shows
---
d083
Third fault
Display of third from last fault message. If the third from last fault message has not been saved, the
display shows
---
d084
Fourth fault
Display of fourth from last fault message. If the fourth from last fault message has not been saved, the
display shows
---
d085
Fifth fault
Display of fifth from last fault message. If the fifth from last fault message has not been saved, the
display shows
---
d086
Sixth fault
Display of sixth from last fault message. If the sixth from last fault message has not been saved, the
display shows
---
d090
Warning
5