A.2
Connections (rear view) DTS 4801.masterclock
DTS 4801 connections
For technical data see in Appendix “I Technical data“
Clamp Connection
Description
L
Mains connection phase
Mains power input with rubber connector
Break point: by disconnecting the rubber connector
See Appendix I, section "Mains power supply"
Mains connection earth
N Mains
connection
neutral
1
DC in power
Input for external DC supply
Ground
2
DC in power supply GND
DTS
Extension
Connection to DTS extension:
Connection length max. 0.5m.
Do only connections when power is off.
3 RS232
TXD
Output for serial telegrams
Connection length max. 30m
4
RS232 RXD*
Input for serial telegrams
5 GND
6
RS485 A
Output for RS 485 slave clock line / serial telegrams
7
/RS485 B
Output for RS 485 slave clock line / serial telegrams
8
Alarm inputs:
18-36VDC, max. 6mA current consumption, close contact.
Contact closed
no alarm.
Length of connection max. 30m.
9
Alarm input 1
10 Common
+
11
Alarm input 2
12 Common
+
13
Alarm input 3
14 Common
+
15
Alarm input 4
16
DCF input +
DCF input e.g. for the connection of a GPS 4500 or DCF
receiver with current loop output.
17
DCF input -
18
DCF
DCF or pulse output, current loop passive, Umax=30VDC,
I
on
= 10..15mA, I
off
< 1mA @20VDC
19
DCF output -
20
Slave clock line a
Output for MOBALine, impulse line or DCF active line
21
Slave clock line b
Output for MOBALine, impulse line or DCF active line
22
IRIG a
Output for IRIG-B (Option)
23
IRIG b
Output for IRIG-B (Option)
24
DC
DC output for GPS 4500 or RS 485 slave clocks
28 VDC, max. 400 mA
25
DC output GND
26
Alarm relay
Alarm Kontakt, öffnet bei Alarm-
Load: 30 W (60 VDC or 1A) or 60 VA (30 VAC or 1A)
27 Alarm
relay
* At the moment only partly available.
!