© MOBATIME
113 / 120
800652.11
Impulse line output
Alternatively to the MOBALine clock line or DCF active line
DTS 4801.masterclock: 1 line
DTS 4802.masterclock: 2 lines: max. current = sum of both lines
Current:
up to 1000 mA impulse current (total)
Voltage:
24 VDC (polarized) (depending on power supply)
Line modes:
1 min., ½ -min., 1/5-min., 1/8-min., 1 sec
Impulse length: 200 – 30'000 ms, approx. 50 ms resolution
Pause length:
200 – 30'000 ms, approx. 50 ms resolution
Acceleration modes: 12 h, 24 h, 1 week
Max. time deviation against internal time: +/- 1 ms
At least 23.5 VDC power supply required
DCF active line
Alternatively to the MOBALine clock line or impusle clock line
DTS 4801.masterclock: 1 line
DTS 4802.masterclock: 2 lines: max. current = sum of both lines
Current:
up to 1000 mA impulse current (total)
Voltage:
24 VDC (polarized) (depending on power supply)
Line modes:
See diagramm in chapter 6.5.5.
Max. time deviation (pulse start) against internal time: +/- 1 ms
At least 23.5 VDC power supply required
IRIG-B output (option)
With built in IF 488 interface. The line has to be run in MOBALine mode.
(Only DTS 4801 IRIG-B: Art. Nr.: 203495).
Impedance:
600
Voltage:
Amplitude
2 Vp-p
Max. time deviation against internal time: +/- 15 ms, jitter < 10 ms
RS 485 line output
(Only DTS 4801).
Alternatively to serial telegrams
Number of monitored clocks:
max. 31
Max. time deviation against internal time: +/- 10 ms, jitter < 10 ms
Communication
RS485, 19200, 8, n, 1, no flow control,
MOBA-RS485-protocol
DCF / pulse output
DCF time code or pulse output selectable.
Passive current loop
Umax = 30 VDC, I
on
= 10..15 mA, I
off
< 1 mA @20VDC
Cable length max. 30 m (not in the 3 m range of a catenary wire (railway)).
DCF output:
time zone selectable
Pulse mode:
second, minute, hour,
user defined interval: 1-3600sec.
Pulse length:
20 – 500 ms, jitter pulse length: +/- 2 ms
Max. time deviation against internal time: +/- 1 ms,
jitter first pulse edge < 0.5 ms
Alarm contact
Opening relay contact (alarm active
contact open).
Switching load: 30 W (60 VDC or 1 A)
or 60 VA (30 VAC or 1 A)
Alarm reporting /
Alarm contact
see Alarm contact
Error messages
see
SNMP-Notification
see
SNMP-Trap
Display
see
Display
Alarm
LED
-
Display
2 lines with up to 16 characters for the display of status information.
DC power supply
24 - 28 VDC / 1.5 A (28 V required for MOBALine)
Mains power supply
90 – 240 VAC / 50 - 60 Hz / max. 30 VA
Typical: < 5 VA @ 230 VAC (without external load)
Power supply output
Nominal 28 VDC, max. 400 mA
Summary of Contents for DTS 4801.masterclock