© MOBATIME
112 / 120
800652.11
Netzwork services
NTP
UDP, Port 123
see timeserver
SNTP
UDP, Port 123
see timeserver
TIME
TCP/UDP, Port 37
see timeserver
DAYTIME
TCP/UDP, Port 13
see timeserver
Telnet
TCP, Port 23
operation
SSH
TCP, Port 22
operation
SCP
über SSH
update
SFTP
über SSH
update
FTP
TCP, Port 21
update
SNMP
UDP, Port 161
operation
UDP, Port selectable (162) alarm notification, see SNMP
SMTP
TCP, Port selectable (25) alarm mail see E-Mail
DHCP
UDP, Port 68
dyn. address allocation (client)
DNS
TCP/UDP, Port 53
address resolution (client)
DHCPv6
only
IPV6
ECHO ICMP
“Ping“
SNMP
V1, V2c, V3 with MD5 for authentication and DES for encryption (privacy).
Alarm reporting via SMTP.
Authentication at the mail server:
- with sender address
- with username/password SMTP-Auth with LOGIN,
PLAIN (RFC 4954) or CRAM-MD5 (RFC 2195)
no “POP before SMTP“
Serial interface
D-Sub 9 (male): (RS232, 38400, 8, n, 1, no flow control)
(front side)
Cable length max. 3 m.
Serial interface
Alternatively to RS485 clock line
(back side)
RS232 or RS485 (RS485 only in DTS 4801)
Max. time deviation against internal time: +/- 10 ms, jitter < 10 ms
300-38400 Bauds, 7 or 8 Data bits, Parity: no, even, odd,
Stop bit: 1 or 2, no flow control), cable length max. 3 m
The description of the telegram functions is provided in Appendix E.
NMEA 0183 without additional synch. pulse:
ZDA telegram, 4800 bauds, 8, 1, none
USB plug
USB Host for USB stick
DCF Input
DCF77 or DCF from GPS receiver (GPS 4500), current loop
Timezone:
selectable
Nominal 28 VDC, max. 32mA, response threshold 8mA
Alarm inputs
4 alarm inputs are available for the monitoring of external devices or as
switch input for switch channels (daylight sensor)
18 – 36 VDC, max. 6 mA, close contact.
External contact closed
no alarm.
Cable length max. 30 m (not in the 3 m range of a catenary wire (railway)).
MOBALine output
Alternatively to the impulse clock line or DCF active line
DTS 4801.masterclock: 1 line
DTS 4802.masterclock: 2 lines: max. current = sum of both lines
Current:
up to 700 mA eff. (total)
Voltage:
without
load
17 VAC, typical 15 VAC
Line modes:
10 sec.-, ½ min.- or 1 min. steps
Max. time deviation against internal time. +/- 10 ms
MOBALine with switching function, switching function for clock illumination
and World time function available.
At least 28 VDC required