© MOBATIME
30 / 120
800652.11
6.5.4 Impulse
line
Impulse clock line with display of the line number:
1. Select line type: 0 = MOBALine, 1 = Impulse line, 2 = DCF active code line
2. Select line function: Line switched off, line switched on
3. Select line mode: Minute steps, ½ minute steps, 1/5 minute steps, 1/8 minute
steps, second steps
4. Select time zone (see chapter “6.5.28 Time zone selection“)
5. Select maximum current (0-1,000mA) on the line. The line will be switched off as
long as the overcurrent is connected.
DTS 4802: The maximum current is divided between both lines, i.e. it can always
only be the remainder at the most that can be set as maximum current.
6. Line time with the format: “hh:mm:ss YY.MM.DD“
7. Pulse time (200-30000ms, resolution approx. 50ms)
8. Pause time in catch-up (200-30000ms, resolution approx. 50ms)
9. Catch-up mode: 12 hrs, 24 hrs, 1 week
Important:
Changes can only be undertaken when the clock line is switched off!
t
PD
t
Mode
t
PD
t
PP
Normal operation
Acceleration
t
PD
: Pulse
time
t
PP
: Pause
time
t
Mode
:
Impulse interval is determined by the line mode (e.g. min = 1 minute)