© MOBATIME
91 / 120
800652.11
10.2 Combination of the signals
Switch
program
channel x
Alarm inputs 1-4
Switch function
(sunrise resp.
sunset)
AND
OR
EXCLUSIVE
MOBALine
RS 485 clock line
ON
OFF
Menu
"Actual channel condition /
manual control"
Menu
"Control Inputs"
and Menu
"Switch function
twilight"
Each of the 4 alarm inputs can as control input or switch input be linked to a channel
with AND, OR, or exclusive.
If the control input is exclusive, the switch status is transmitted as quickly as possible
via MOBALine (0-10sec).
If the control input AND or OR is linked to the switch program, the status of the input is
transferred to the next but one minute.
The switch inputs have priority as opposed to the twilight function:
i.e. if a control input and the twilight function is linked to the same channel, the twilight
function is ignored.
If an alarm input is used as switch input, it must be masked in all alarm masks.
10.3 Behavior at start-up, exchange of switch program file
After starting up the DTS 480x, or after changing the program file, it can take up to 2
min until the switch states to the channel relay are correct.
Important:
The max. number of signal commands is limited to 15 per minute.