4 - 13 4 - 13
MELSEC-Q
4 SETUP AND PROCEDURES BEFORE OPERATION
(b) When switching the mode using the setting of the mode switching setting
(buffer memory addresses 158, 159: Un\G158, Un\G159) and operating
condition setting request (Y9)
Switches to offset/gain
setting mode
Common program
Switches to
normal mode
Processing in normal mode
Sets 4144
H
to buffer memory
address 158.
Sets 964
H
to buffer memory
address 159.
Turns ON operating condition
setting request (Y9).
Turns OFF operating condition
setting request (Y9)
Sets 964
H
to buffer memory
address 158.
Sets 4144
H
to buffer memory
address 159.
Turns ON operating condition
setting request (Y9).
Turns OFF operating condition
setting request (Y9).
(c) When switching the mode by making intelligent function module switch
setting, other than the common program is not required.