7 - 24 7 - 24
MELSEC-Q
7 ONLINE MODULE CHANGE
7.3.5 When user range setting is used and initial setting was made with sequence program
(other system is available)
(1) Conversion
disable
(a) Set Conversion enable/disable setting (buffer memory address 0: Un\G0)
for all channel conversion disable and turn the operating condition setting
request (Y9) from OFF to ON to stop conversion.
After confirming that conversion has stopped with the Conversion
Completion Flag (buffer memory address 10: Un\G10), turn off Operating
Condition Setting Request (Y9).
Summary of Contents for q64rd
Page 1: ......
Page 2: ......
Page 62: ...3 39 3 39 MELSEC Q 3 SPECIFICATIONS MEMO ...
Page 92: ...5 17 5 17 MELSEC Q 5 UTILITY PACKAGE GX Configurator TI X Y Monitor Test 1 OMC refresh ...
Page 98: ...5 23 5 23 MELSEC Q 5 UTILITY PACKAGE GX Configurator TI MEMO ...
Page 175: ......
Page 176: ......