5 - 4 5 - 4
MELSEC-Q
5 UTILITY PACKAGE (GX Configurator-TI)
(6) Number of parameters that can be set in GX Configurator-TI
When multiple intelligent function modules are mounted, the number of
parameter settings must not exceed the following limit.
Maximum number of parameter settings
When intelligent function modules are
installed to:
Initial setting
Auto refresh setting
Q00J/Q00/Q01CPU 512
256
Q02/Q02H/Q06H/Q12H/Q25HCPU 512
256
Q02PH/Q06PH/Q12PH/Q25PHCPU 512
256
Q12PRH/Q25PRHCPU 512
256
Q02UCPU 2048
1024
Q03UD/Q04UDH/Q06UDH/Q13UDH/
Q26UDH/Q03UDE/Q04UDEH/
Q06UDEH/Q13UDEH/Q26UDEHCPU
4096 2048
MELSECNET/H remote I/O station
512
256
For example, if multiple intelligent function modules are installed to the
MELSECNET/H remote I/O station, configure the settings in GX Configurator so
that the number of parameter settings for all the intelligent function modules does
not exceed the limit of the MELSECNET/H remote I/O station.
Calculate the total number of parameter settings separately for the initial setting
and for the auto refresh setting.
The number of parameters that can be set for one module in GX Configurator-TI
is as shown below.
Target module
Initial setting
Auto refresh setting
Q64RD
5 (Fixed)
17 (Max.)
Q64RD-G
4 (Fixed)
18 (Max.)
Example) Counting the number of parameter settings in Auto refresh setting
This one row is counted as one setting.
Blank rows are not counted.
Count up all the setting items on this
screen, and add the total to the number of
settings for other intelligent function
modules to get a grand total.