3 - 33 3 - 33
MELSEC-Q
3 SPECIFICATIONS
(6) When the settings below are applied, an error (error code 6
) occurs. Then the
error flag (XF) turns ON and the operation is carried out with the setting before the
error occurrence.
(a) Setting a value out of the above settable range.
(b) Setting a value that does not satisfy the following condition:
Warning output lower lower limit value
≤
lower upper limit value
≤
upper lower
limit value
≤
upper upper limit value
(7) If the lower upper limit value is equal to the upper lower limit value, no error will
occur and the warning output is made invalid.
(8) The Operating Condition Setting Request (Y9) must be turned on/off to make the
setting valid.