7 - 18 7 - 18
MELSEC-Q
7 ONLINE MODULE CHANGE
(d) Monitor the measured temperature values (16 bits) (buffer memory
addresses 11 to 14: Un\G11 to 14) or measured temperature values (32
bits) (buffer memory addresses 54 to 61: Un\G54 to 61) to check that
proper conversion has been made.
(5) Resumption of control
(a) After choosing [Diagnosis] - [Online module change] on GX Developer to
redisplay the "Online module change" screen, click the [Execution] button to
resume control. The FROM/TO instruction for the module resumes.
(b) The "Online module change completed" screen appears.
Summary of Contents for q64rd
Page 1: ......
Page 2: ......
Page 62: ...3 39 3 39 MELSEC Q 3 SPECIFICATIONS MEMO ...
Page 92: ...5 17 5 17 MELSEC Q 5 UTILITY PACKAGE GX Configurator TI X Y Monitor Test 1 OMC refresh ...
Page 98: ...5 23 5 23 MELSEC Q 5 UTILITY PACKAGE GX Configurator TI MEMO ...
Page 175: ......
Page 176: ......