1 - 4 1 - 4
MELSEC-Q
1 OVERVIEW
1.2 Added/Changed Functions
Functions added or changed for the Q64RD/Q64RD-G are shown below.
(1) Q64RD
Functions added or changed for the Q64RD are shown below.
Item Applicable
module
Function
overview
Reference
section
Online module
change
Function version C
or later
You can change the module without stopping the system.
The CPU of function version C or later is required.
Chapter 7
Using the mode switching setting (buffer memory addresses 158, 159:
Un\G158, Un\G159) and operating condition setting request (Y9), the
module is switched between the normal mode and offset/gain setting
mode without the CPU being reset.
Section
3.4.24
Using the dedicated instruction (G(P).OFFGAN), the module is
switched between the normal mode and offset/gain setting mode
without the CPU being reset.
Appendix
3.2
Mode
switching that
does not
require CPU to
be reset
Function version C
or later
Using GX Configurator-TI, the module is switched between the normal
mode and offset/gain setting mode without the CPU being reset.
Section
5.6.2
Conversion
setting for
disconnection
detection
function
First 5 digits of
product information
are 07072 or later
For values to be stored in the CH measured temperature value
(buffer memory addresses 11 to 14, 54 to 61: Un\G11 to 14, Un\G54 to
61) in the case of disconnection detection, any of "Value immediately
before disconnection", "Up scale (maximum value of measured
temperature range + 5% of measured temperature range)", "Down
scale (minimum value of measured temperature range – 5% of
measured temperature range)" or "Given value" can be selected.
Section
3.2.2
Moving
average
First 5 digits of
product information
are 07072 or later
Digital output values sampled at specified number of times are
averaged.
Section
3.2.1
Primary delay
filter
First 5 digits of
product information
are 07072 or later
By a preset time constant, digital output values are smoothed.
Section
3.2.1
(2) Q64RD-G
The following is a function added for the Q64RD-G.
Item
Applicable version
Function overview
Reference
section
Conversion
setting for
disconnection
detection
function
First 5 digits of
product information
are 07072 or later
For values to be stored in the CH measured temperature value
(buffer memory addresses 11 to 14, 54 to 61: Un\G11 to 14, Un\G54 to
61) in the case of disconnection detection, any of "Value immediately
before disconnection", "Up scale (maximum value of measured
temperature range + 5% of measured temperature range)", "Down
scale (minimum value of measured temperature range – 5% of
measured temperature range)" or "Given value" can be selected.
Section
3.2.2
POINT
(1) Refer to Appendix 2.1 for the function comparison between function versions.
(2) For differences between the Q64RD/Q64RD-G whose first 5 digits of product
information are 07071 or earlier and those of 07072 or later, refer to Appendix
2.2.
(3) Refer to Section 2.2 for how to check the function version and product information.