7 ONLINE MODULE CHANGE
7.3.4 When user range setting is used and initial setting was made with GX Configurator-TI
(other system is unavailable)
(1) Conversion
disable
(a) Set "Disable" in the Setting value field of Conversion Enable/Disable
Setting on the CH Monitor/Test screen of GX Configurator-TI, and click
the Execute test button.
(b) After making sure that "Disable" is displayed in the Current value field of
Conversion Enable/Disable Setting, set "Request" in the Setting value field
of Operating Condition Setting Request on the Monitor screen, and click the
[Execute test] button to stop conversion.
Monitor the Conversion Completion Flag (buffer memory address 10:
Un\G10) and confirm that conversion has stopped.