7 ONLINE MODULE CHANGE
7.3.2 When factory default is used and initial setting was made with sequence program
(1) Conversion
disable
(a) Set the Conversion enable/disable setting (buffer memory address 0:
Un\G0) for all channel conversion disable and turn Operating Condition
Setting Request (Y9) from OFF to ON to stop conversion.
After confirming that conversion has stopped with the Conversion
Completion Flag (buffer memory address 10: Un\G10), turn off Operating
Condition Setting Request (Y9).